CAT Switch LEHE4651 04 User Manual

AUTOMATIC TRANSFER SWITCH  
CTS SERIES  
AUTOMATIC  
TRANSFER SWITCH  
The Cat® CTS Series Automatic Transfer Switch  
(ATS) is configurable for applications requiring the  
dependability and ease of operation found in  
a full featured power contactor type transfer switch.  
The CTS Series is equipped with the MX250  
controller that is designed for the most demanding  
transfer or bypass switch applications.  
FEATURES  
DESIGN AND CONSTRUCTION FEATURES  
Double throw, interlocked operation  
Electrically operated, mechanically held  
by a simple, over-center mechanism  
Silver alloy contacts with separate arcing  
contacts on 600 amp and above  
Arc quenching grids, enclosed arc chambers,  
and wide contact air gap for superior source to-  
source isolation on all units  
Control circuit disconnect plug and drive inhibit  
switch for safe maintenance  
Components accessible for inspection and  
maintenance without removal of the switch  
or the power conductors  
ELECTRICAL RATINGS  
Ratings 40 to 4000 amperes  
2, 3 or 4 Poles  
NEMA 1, 3R, 4, 4X and 12  
Available to 600 VAC, 50 or 60 Hz  
Suitable for emergency and standby  
applications on all classes of load,  
100% tungsten rated through 400 amps  
UL 1008 listed at 480 VAC  
CSA C22.2 No. 178 certified at 600 VAC  
IEC 947-6-1 listed through 480 VAC  
PERFORMANCE FEATURES  
Contact transfer speed less than 100  
milliseconds  
High close-in and withstand capability  
Temperature rise test per UL 1008 conducted  
after overload and endurance tests in  
unventilated enclosure – exceeds UL  
requirements  
Mechanical indicator and contact chamber  
cover designed for inspection, safety and  
position designation  
Equipped with the MX250 Control Package  
LEHE4651-04  
 
AUTOMATIC TRANSFER SWITCH  
NEUTRAL SWITCHING  
The CTS Series is available in true four pole designs  
for multi-source power systems that require switching  
the neutral. The neutral contact is on the same shaft  
as the associated main contacts. This design ensures  
positive operation, and prevents any possibility that  
the neutral contact will fail to open or close, as is  
possible when the neutral pole is an add-on  
accessory. The neutral contacts are identical to the  
main contacts, having the same current carrying and  
high withstand /closing ratings as the mains. They are  
designed to break last and make first to negate the  
possibility of transients while switching the neutral.  
SAFE MANUAL OPERATION  
The CTS manual operator consists of a large,  
easy-to-use handle that fits securely for manual  
operation during installation and maintenance  
or in an emergency.  
Every CTS is provided with an operator inhibit  
switch to disconnect the electrical drive prior to  
maintenance. Fully enclosed wrap-around arc  
covers shield the main contacts and mechanical  
components, preventing operator exposure during  
manual operation  
CTS SERIES ATS  
400 amp, 2 pole  
TRANSFERRING LARGE MOTOR  
OR HIGHLY INDUCTIVE LOADS  
3. Series CTSD: The CTSD offers a delayed  
transition on transfer switches 40A and above.  
This programmed center-off position allows for  
the full decay of rotating motors or transformer  
fields. It can also be used for load shedding  
of selected circuits or other applications which  
require a means to disconnect the load from  
either source. Many UPS system manufacturers  
recommend delayed transition switches to  
support sequencing of their systems. Reference  
the CTSD supplement for further details.  
Some loads, especially large motors receive  
severe mechanical stress if power is transferred  
out of phase while the motor is still rotating.  
Also, back EMF generated by a motor can result  
in over currents that can blow fuses or trip circuit  
breakers. The CTS Series offers four solutions  
to these problems:  
1. Optional Universal Motor Disconnect Contact:  
This load control disconnects a large motor via  
its control circuit for an adjustable period of time  
prior to transfer in either direction. For switching  
multiple motors, the motor disconnect contact  
with staged restart disconnects the motors  
prior to transfer and brings them back on line  
sequentially.  
4. Series CTSCT: Cat closed transition  
switches combine CTSD operation during a  
source failure with a highly engineered control  
system that allows momentary paralleling (100  
ms) of two acceptable sources, thereby limiting  
the impact of transfer on the load. Reference  
the CTSCT supplement for further details.  
2. Accessory R50 Phase Monitor: This feature  
compares the phase angle between both sources  
of power and prevents transfer until the two are  
approximately in phase (within a self adjusting  
range). The CTS’s high speed transfer action  
coupled with the MX series microprocessor  
control logic ensure closures at or near zero  
degree phase difference  
LEHE4651-04  
3
 
AUTOMATIC TRANSFER SWITCH  
STANDARD FEATURES (MSTD PACKAGE)  
Sensing (MSEN) Package, includes:  
EXES Functions  
Normal Source Over voltage sensing (3 phase)  
Q7 – Inhibit Transfer to Normal  
S12P – Auto/Manual Selector Switch  
Feature  
6/P  
J2E/J2N  
A3  
L1/L2  
A4  
L3/L4  
Calibrate  
LN/P  
CDT  
P1  
DS  
R50  
DT  
Function  
Momentary Test Switch  
Adj. over/under freq (S1 and S2)  
Aux Contact (S2 position)  
Source Position LEDs  
Aux Contact (S1 position)  
Source Available LEDs  
Volt. and Freq. calibration  
Center-Off Position LCD*  
Load/No-Load Exerciser  
Source 2 Start Time Delay  
Auto/Inhibit Switch (> 600A)  
In-Phase Monitor  
Time Delay – Neutral to S1*  
Transfer Commit  
Time Delay – Neutral to S2*  
Source 1 Stable Time Delay  
Engine Start Contact  
Special (MSPE) Package, includes:  
CONS Functions  
SENS Functions  
S5P – Manual transfer to Normal Switch  
(Replaces S12P)  
Switchgear (MPSG) Package, includes:  
SPES Functions  
Additional set of A3/A4 Contacts  
R15 – Load Shed to “Dead Normal” or  
R15D – Load Shed to Neutral Position*  
S12/P – Auto-Manual Selector Switch  
S13/P  
DW  
T
E
U
EL/P  
Source 2 Stop Time Delay  
Log of last 16 events and  
System Data  
VI  
Voltage Imbalance  
K/P  
W
YEN  
S1 and S2 Freq. Indication  
S2 Stable Time Delay  
Bypass T and W Time Delays  
*Available with Delayed Transition switches only.  
OPTIONAL PACKAGES  
Exerciser (MEXE) Package, includes:  
STDS Functions  
A1/A1E – S1/S2 Failure aux contact  
A3/A4 – One additional contact each  
CDP – Programmable exerciser  
Q2 – Remote Peak Shave/Load Test  
R16 – Phase Rotation Sensing  
Screenshot of ATS operating parameters on Cat  
Switchgear HMI.  
Combined with the optional Modbus  
Communication Card, the PSGS package allows  
for integration with Cat Switchgear. This feature  
allows ATS operating parameters to be displayed  
on the PowerLynx® 3000 HMI as well as on the  
optional Remote Monitoring Software. Supply of  
this feature set affords real-time monitoring of the  
ATS as well as direct control over the following  
parameters from the Switchgear HMI:  
Timer Settings  
Controls (MCON) Package, includes:  
EXES Functions  
Q3 – Remote Inhibit transfer to Emergency  
Q7 – Inhibit Transfer to Normal  
T3/W3 – Elevator Pre-Signal Aux Contacts  
UMD – Universal Motor Load Disconnect  
Pickup/Dropout settings  
Testing Functions  
Alarm functions  
Manual operation  
LEHE4651-04  
4
 
AUTOMATIC TRANSFER SWITCH  
CT  
CTS SERIES ACCESSORY DEFINITIONS  
6P  
CTS SERIES ACCESSORY GROUP MATRIX  
Microprocessor activated test switch (Momentary)  
6A  
Hardwired test switch (Maintained)  
6AP  
Microprocessor activated test switch (Maintained)  
6BK  
Hardwired test switch (Maintained Auto – Momentary Test)  
Key operated  
6CK  
Hardwired test switch (Maintained Auto – Maintained Test)  
Key operated  
A1  
Auxiliary Contact S.P.D.T. – Normal (Source 1) Failure  
A1E  
Auxiliary Contact S.P.D.T. – Emergency (Source 2) Failure  
A3  
Auxiliary Contact – closed in emergency (Source 2) Additional  
available (10 max.) on CTS Series and need to be specified  
A4  
Auxiliary Contact – closed in normal (Source 1) Additional  
available (10 max.) on CTS Series and need to be specified  
A62  
Motor disconnect and staged restart (1 contact)  
AB3  
Auxiliary contact – closed in bypass emergency (Source 2)  
(S.P.D.T.) (Standard up to 400A) Additional available (10 max.)  
on CBTS Series and need to be specified  
AB4  
Auxiliary contact – closed in bypass emergency (Source 1)  
(S.P.D.T.) (Standard up to 400A) Additional available (10 max.)  
on CBTS Series and need to be specified  
CALIBRATE  
Microprocessor activated calibration feature  
CDP  
Programmable exerciser daily, 7/14/28/365 days  
user-selectable, with or without load  
CDT  
CTS SERIES ACCESSORY DEFINITIONS  
(continued)  
Exerciser no load timer  
CTAP  
Chicago transfer alarm panel mounted in door of enclosure.  
Includes 3 aux. contacts and fuse.  
DS  
Disconnect Switch. Disconnects source voltage to transfer  
power panel.  
DT (DELAYED TRANSITION ONLY)  
Time Delay from Neutral Switch position to Source 2  
on retransfer  
DW (DELAYED TRANSITION ONLY)  
Time Delay from Neutral Switch position to Source 2  
on retransfer  
HT(1)(2)  
Heater and Thermostat 208/240V (1) 380/600V (2)  
mounted and  
inter-wired in enclosure. (requires larger enclosure for  
40-200A)  
K
Frequency Meter (Analog) – Door mounted  
K/P  
Frequency Indication on the controller  
LNP  
Center-off position LCD-Indicator  
L1  
LED light indicates Switch in Source 2 position  
L2  
LED light indicates Switch in Source 1 position  
L3  
LED light indicates Source 1 available  
L4  
LED light indicates Source 2 available  
E
Engine Start Relay  
EL/P  
Event log of last 16 events  
ETHERNET  
Ethernet Communication Adapter. Requires Modbus  
Communication Module.  
F
Fan contact, closed when engine runs.  
LEHE4651-04  
5
 
AUTOMATIC TRANSFER SWITCH  
CTS SERIES ACCESSORY DEFINITIONS (continued)  
R16  
LonWorks  
Phase rotation sensing of Normal (Source 1) and  
Emergency (Source 2)  
LonWorks Communication Module  
M1  
R26/R26D  
Single Phase Amp Meter (Analog)  
Interruptible Power Rate Provisions. Allow transfer out  
of Source 1 position to Mid position or dead Source 2.  
Alarm and Pre-Signal circuit included. (Need to specify  
voltage – 120 VAC, 24 VAC, 24 VDC  
R50  
M2  
Three Phase Amp Meter (Analog)  
M90  
EPM2000 True RMS Digital Meter with display (Amps, Volts,  
Power, Energy, Power Factor and Frequency). 3 Line LED  
In Phase monitor between Normal (Source 1) and  
Emergency (Source 2) to allow transfer  
S5P  
Display. 50/60 Hz Universal Operation. 1 or 3 phase. Standard  
Modbus RTU RS485 communications capability.  
M90A  
Microprocessor activated auto/manual retransfer  
selector switch for transferring to Normal (Source 1)  
(includes microprocessor activated YN accessory)  
S12P  
Includes Modbus communication card and factory wiring  
between EPM2000 and Modbus communication card.  
M90B  
Includes Modbus communication card, Ethernet communication  
Microprocessor activated auto/manual retransfer  
selector switch for transferring to Normal (Source 1)  
(includes microprocessor activated YN & YE accessory)  
S13P  
adapter and factory wiring between EPM2000 and Modbus  
communication card.  
M91  
EPM6000 True RMS Digital Meter with display (Amps, Volts,  
Microprocessor activated commit/no commit on  
transferring to Emergency (Source 2) (with  
enable/disable settings)  
Power, Energy, Power Factor and Frequency, THD). Certified  
energy and demand metering. Meets ANSI C12.20 and IEC  
687 Accuracy Classes. Front IrDA Port Laptop Connection.  
S14K  
Standard Modbus RTU RS485 or DNP 3.0 communications  
Keyed selector switch for retransfer to normal-test-auto  
SW1  
capability.  
M91A  
Auto/Off/Start Engine control selector – Door mounted  
(keyed or non-keyed operation available)  
SW2  
Includes Modbus communication card and factory wiring  
between EPM6000 and Modbus communication card.  
M91B  
Auto/Off Engine control selector – Door mounted  
(keyed or non-keyed operation available)  
SW3  
Includes Modbus communication card, Ethernet communication  
adapter and factory wiring between EPM6000 and Modbus  
communication card.  
Source Priority Selector Switch – Door mounted. Allows  
selection of Source 1 or Source 2 to be the Prime  
Source. Transfer Switch will transfer to selected Prime  
Source if that Source is available. (keyed or non-keyed  
operation available)  
Modbus  
Modbus RTU Communication Module  
N1  
Running Time Indicator – Door mounted  
N2  
T
Operation Counter – Door Mounted  
Retransfer to Normal (Source 1) adjustable time delay  
T3/W3  
P1  
Engine Start Timer (adjustable to 6 seconds)  
Pre-signal contact on transfer to Normal (Source 1) or  
Emergency (Source 2) during test  
U
P2  
Engine Start Timer – Extended time delay (adjustable to  
300 seconds)  
Engine stop /cool adjustable cool down timer  
UMD  
Pre and post transfer output adjustable time range.  
Functions in both directions. Includes 2 circuits.  
(Additional circuits available).  
Q2  
Peak shave/remote load test/area protection – Relay (S.P.D.T.)  
(Need to specify voltage – 120 VAC, 24 VAC, 24 VDC – 120V  
default standard)  
Q3  
VI  
Inhibit transfer to emergency (Source 2) (load add relay) – Relay  
(S.P.D.T.) (Need to specify voltage – 120 VAC, 24 VAC,  
24 VDC – 120V default standard)  
Voltage imbalance between phases (3 Phase only)  
W
Adjustable time delay on transfer to Emergency  
(Source 2)  
YEN  
Bypass transfer timers function (soft key switch in  
microprocessor)  
Q7  
Inhibit transfer to normal (Source 1) – Relay (S.P.D.T.) (Need to  
specify voltage – 120 VAC, 24 VAC, 24 VDC – 120V default  
standard)  
R1-1/R1-3  
Over Voltage sensing for normal (Source 1) single (R1-1)  
or three (R1-3) phase  
R15/R15D  
Load Shed. Should Source 2 become overloaded, a signal can  
be given to switch to the Neutral position.  
LEHE4651-04  
6
 
AUTOMATIC TRANSFER SWITCH  
CTS SERIES DIMENSIONAL SPECIFICATIONS  
CTS Series Transfer Switches  
NEMA 1 Enclosed  
Ampere  
Rating  
Height  
(A)  
Width  
(B)  
Depth  
(C)  
Reference  
Figure  
Application  
Notes  
Poles  
Weight  
40,80, 100 & 150  
225, 260 & 400  
600  
2,3  
4
24 (610)  
24 (610)  
18 (457)  
18 (457)  
24 (610)  
24 (610)  
40 (1016)  
40 (1016)  
40 (1016)  
40 (1016)  
36 (914)  
36 (914)  
36 (914)  
36 (914)  
47 (1194)  
47 (1194)  
11 (279)  
11 (279)  
14 (356)  
14 (356)  
20 (508)  
20 (508)  
20 (508)  
20 (508)  
48 (1219)  
48 (1219)  
48 (1219)  
48 (1219)  
62 (1575)  
62 (1575)  
A
A
A
A
B
B
B
B
C
C
C
C
C
C
57 (26)  
60 (27)  
1-7  
1-7  
1-8  
1-8  
1-8  
1-8  
1-11  
2,3  
4
46 (1168)  
46 (1168)  
74 (1880)  
74 (1880)  
74 (1880)  
74 (1880)  
90 (2286)  
90 (2286)  
90 (2286)  
90 (2286)  
90 (2286)  
90 (2286)  
165 (75)  
170 (68)  
2,3  
4
380 (172)  
430 (195)  
455 (206)  
540 (245)  
1010 (458)  
1160 (526)  
1130 (513)  
1395 (633)  
1595 (723)  
1850 (839)  
800, 1000 & 1200  
1600 & 2000  
3000  
2,3  
4
3
4
3
4
4000  
3
4
Application Notes :  
1. Dimensions are listed in inches (mm) and weights in pounds (kg).  
2. Includes 1.25" door projection beyond base depth. Allow a minimum of 3" additional depth for projection of handle, light,  
switches, pushbuttons, etc.  
3. All dimensions and weights are approximate and subject to change without notice and are not for construction use.  
4. Special enclosures (NEMA 3R, 4, 12, etc.) may include mounting tabs, etc. Consult the published dimension drawings for details.  
5. Normal and emergency may be ordered inverted on any switch. The load may be inverted 500-1200 amps.  
Consult the factory for details.  
6. Special lug arrangements may require different enclosure dimensions. For certified drawings, contact Caterpillar.  
7. Packing materials must be added to weights shown. Allow 15% additional weight for cartons, skids, crates, etc.  
8. Add 4" in height for removable lifting lugs.  
9. 4000 amp depth dimension shown is standard. Depending on your cable/conduit requirements you may desire a deeper  
enclosure. Consult Caterpillar for further details.  
10. Lug adapters for 3000-4000 amp limits may be staggered length for ease of entrance. Consult Caterpillar for details.  
11. Ventilation louvers on side/rear of enclosure at 3000 and 4000A. One side or rear must be clear to afford proper airflow.  
LEHE4651-04  
7
 
AUTOMATIC TRANSFER SWITCH  
AL-CU UL LISTED SOLDERLESS SCREW-TYPE TERMINALS  
FOR EXTERNAL POWER CONNECTIONS  
Normal, Emergency  
& Load Terminals  
Normal, Emergency  
& Load Terminals  
Switch Size  
Amps  
Cables  
Range of  
Switch Size  
Amps  
Cables  
Range of  
per Pole  
Wire Sizes  
per Pole  
Wire Sizes  
40-80  
100-225  
260  
#8 to 3/0 AWG  
800/1000/1200  
1600  
#2 AWG to 600 MCM  
600 MCM  
4
#6 AWG to 250 MCM  
#6 AWG to 350 MCM  
#4 AWG to 600 MCM  
#2 AWG to 600 MCM  
1
2
2000  
8
400  
3000  
600  
4000  
NOTES:  
*
Line and load terminals are located in rear and arranged for bus bar connection.  
1. Special terminal lugs and neutral bars are available at additional cost.  
Contact factory and advise cable sizes and number of conductors per pole.  
2. Fully rated solid neutral (3x standard normal power connector) provided when required by system voltage.  
3. Normal and emergency may be ordered inverted on any switch. Load may be inverted 600-1200 amps.  
Consult the factory for details.  
4. Lug adapters for 3000-4000 amp units may be staggered length for ease of entrance. Consult the factory for details.  
5. Special lug arrangements may require different enclosure dimensions. For certified drawings, contact Caterpillar  
Information contained in this publication may be considered confidential. Discretion is recommended when distributing.  
Materials and specifications are subject to change without notice.  
CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow,” the “Power Edge” trade dress as well as corporate  
and product identity used herein, are trademarks of Caterpillar and may not be used without permission.  
©2012 Caterpillar  
All Rights Reserved.  
Printed in U.S.A.  
LEHE4651-04 (11/12)  
 

Black Box Computer Hardware HD over IP Encoder Decoder User Manual
Bogen Car Amplifier HTA 125A User Manual
Bosch Appliances Home Security System MIC612 User Manual
Bosch Appliances Security Camera VG5 600 User Manual
Bushnell Telescope 78 8830 User Manual
Cannon Time Clock PIXMA MX340 User Manual
Casio Clock DQR 200 User Manual
Chariot Carriers Baby Carrier 51100452 User Manual
Christie Digital Systems Projector LX66A User Manual
Chromalox Electric Heater GS User Manual